BESA flags fire damper safety issue

UK: Inspections carried out by maintenance contractors have revealed that a “huge number” of fire and smoke dampers have been incorrectly installed in building ventilation systems.

The Building Engineering Services Association (BESA) has taken the unusual step in issuing an urgent warning after inspections found potential fire safety weakness in a large number of building ventilation systems.

It has issued an interim technical bulletin (VH001) ahead of a full update of its industry guidance for the Installation of Fire Dampers and Smoke Dampers (DW145) which is due for launch at the Association’s National Conference in October.

Head of technical Graeme Fox explained that many did not comply with manufacturers’ instructions and needed remedial action “without delay”.

“We have been alerted to the very dangerous practice of using self-drilling ‘tek’ screws which do not melt when temperatures rise during a building fire. This means spring-loaded dampers will not be released to contain the spread of fire within the zone and ensure the integrity of the fire stopping measure,” he said.

“Dampers must be secured by fusible fixings that allow the duct to break away otherwise the collapsing duct could pull the damper out of place and break the seal between the fire zones,” added Fox.

BESA’s technical committee sanctioned the technical bulletin, which is freely available on the Association’s website, to give contractors the information and appropriate terminology to alert clients to this potentially life-threatening problem.

The bulletin also updates the guidance and statutory requirements covering installation, testing and maintenance of fire dampers and smoke dampers including clients’ legal obligations to ensure their fire safety systems remain fit for purpose in line with the Regulatory Reform (Fire Safety) Order 2005 for England and Wales and the Fire Safety (Scotland) Regulations 2006.

It outlines the crucial role played by the penetration seal in ensuring the overall fire stopping integrity of an installation, the importance of maintenance teams being able to find and access dampers for testing and repair, and the need for designers and installers to seek expert advice from damper manufacturers.

“While this is clearly a very worrying situation, we can take some reassurance from the fact that this problem is being brought to our attention by the increasing frequency of fire damper inspections and tests as awareness grows of this extremely important issue,” said Fox.

“We would urge contractors to alert their clients immediately so all the necessary checks and repairs can be carried out.”

The document can reviewed and downloaded here.

Latest News

27th August 2026

Cellar coolers are refrigeration equipment

UK: The British Refrigeration Association has welcomed confirmation that restrictions on single-split air conditioning systems under the GB F-gas regulations do not apply to systems used solely for cooling products.
26th August 2026

Carly Gayle named LCL Trainee of the Year

UK: Carly Gayle, one of Baxi’s newest F-gas engineers, has been named Trainee of the Year by awarding and certification organisation LCL Awards.
26th August 2026

Copeland Europe’s Sandro Matic moves to US

USA/GERMANY: Sandro Matic, president of Copeland’s European business, is to become president of its Americas business. He will be replaced by Gwenaelle Cheramy, currently general manager of Honeywell in Switzerland.
26th August 2026

IOR looks for STEM Ambassador volunteers

UK: The Institute of Refrigeration is seeking more industry professionals to volunteer as STEM Ambassadors to help students understand the vital role RACHP technologies and the career opportunities available.
25th August 2026

Data centre thermal management kits for Autodesk

USA: Trane Technologies has Introduced data centre thermal management kits in Autodesk Revit and Autodesk Forma.
25th August 2026

Carrier launches engineless multi-temperature TRU

USA: Carrier Transicold’s Vector 8200 is the company’s first engineless multi-temperature TRU, offering single- and multi-temperature capabilities for stationary trailer cold storage.