Leak testing with oxygen caused heat pump blast

POLAND: Authorities in Opole have concluded that the heat pump explosion in Chrząstowice that killed two people last year was caused by using oxygen to carry out pressure tests.

The heat pump explosion on August 20, 2024, killed two people, a 30-year-old engineer, who was servicing the unit, and the 45-year-old property owner. They were said to have suffered multiple injuries to the chest, head, arms and legs. A third individual was injured and taken to hospital.

The Nowa Trybuna Opolska website quotes the district prosecutor’s office as saying: “According to our findings, the explosion was caused by the use of technical oxygen to check the system for leaks. It mixed with oil vapours from the pump’s external unit, causing a violent ignition and explosion, which ultimately ruptured the structural elements of the device, which struck the injured parties.”

Pressure testing a DX system with oxygen instead of a non-reactive gas like nitrogen is extremely dangerous. The oxygen can react violently with oils and grease present in the system, leading to potential explosions. 

The attorney for one of the victims has filed an appeal against the decision.

The explosion was said to have torn the heat pump apart with metal fragments damaging the walls and roofs of neighbouring houses. A fragment of the casing was found in the parking lot of a store 300m away. The air-to-water unit was using R410A.

Related stories:

Incorrect pressure testing caused heat pump explosion – 9 March 2025
POLAND: Investigators looking into the fatal domestic heat pump explosion in Chrząstowice in August, have revealed that the cause was the failure to use a non-reactive gas during pressure testing. Read more…

UPDATE: Fatal heat pump explosion – 23 August 2024
POLAND: While official investigations continue into the fatal heat pump explosion in Chrząstowice, more details have emerged regarding the incident. Read more…

Heat pump blamed for fatal explosion – 21 August 2024
POLAND: A domestic heat pump explosion has been blamed for the deaths of two people in Chrząstowice, south-west Poland. Read more…

Latest News

14th October 2026

Arkema launches new R134a replacement

FRANCE: Arkema has announced the release of R516A, a new, lower GWP refrigerant replacement for R134a in HVAC and cooling applications.
13th October 2026

Hitachi launches Air365 Max (Pro) R32 VRF

GERMANY: Launched at this week’s Chillventa show, Air365 Max (Pro) is Hitachi’s latest VRF system for commercial projects and using R32 refrigerant.
13th October 2026

Panasonic adds compact R290 heat pumps

GERMANY:  Panasonic has introduced new compact residential indoor and outdoor units to its Aquarea M Series of R290 air-to-water heat pumps.
13th October 2026

Cyber firm claims over 800 UK supermarkets vulnerable to attack

UK: An internet scan has revealed that more than 800 refrigeration and BMS controllers in the UK are vulnerable to a cyberattack similar to those experienced in France this week.
13th October 2026

Security firm warns on refrigeration asset security

USA: Following Sunday night’s cyberattack on French supermarkets, security company Claroty has warned food retailers that they should not assume that their refrigeration controllers are isolated and secure.
12th October 2026

Danfoss moves to mitigate cyberattack

FRANCE: Danfoss has said it is in close contact with supermarket customers in France affected by a cyberattack on Sunday night on its refrigeration controllers.